Air Barrier Materials, Components, Assemblies & Systems
Air Barrier Assemblies
An air barrier assembly is a collection of air barrier materials (ie. self-adhered sheet air barriers, liquid applied membranes, medium density sprayed polyurethane foam, mechanically fastened commercial building wraps and boardstock air barriers) and air barrier accessories (ie. sealants, tapes and transition membranes) assembled together to form a continuous barrier to air infiltration into the environmental separator. The performance of an air barrier assembly is of far greater importance that the air permeance of the material. When materials and accessories are installed proficiently, the benefits of the assembly have positive benefits for the entire life cycle of the building.
Testing of Air Barrier Assemblies
The testing of an air barrier assembly for air leakage is completed in accordance with ASTM E2357 Standard Test Method for Determining Air Leakage of Air Barrier Assemblies. ABAA defines an air barrier assembly as one that has a air leakage rate less than 0.2 L/(s•m2) @ 75 Pa (0.04 cfm/ft2 @ 1.56 lb/ft2). Specimen one of the test is a 8' x 8' wall with exterior panel-type material. The joints are sealed and the air barrier is applied to form a continuous assembly. The second specimen is a 8' x 8' wall with exterior panel-type material, a 24" x 48" window rough opening, masonry ties, junction boxes, galvanized duct and a PVC pipe. The panel joints and penetration joints are sealed and the air barrier material then applied. The cumulative results of this test specimen will include the air permeance of the material, accessories, air barrier components (window and services elements) and the air leakage that results from joining those three parts together. See the image below for the specimens tested as per ASTM E2357.
Specimen 1 - Opaque Wall
Specimen 2 - Continuity at Penetrations
Foundation Interface and Opaque Wall (with Modifications)
Air Barrier Assembly Test Requirements for ABAA Listing
For an assembly to be listed on the ABAA website, manufacturers must provide a E2357 test report, information (ie. master spec and/or installation instructions) on what materials (thickness installed – if applicable), accessories and their sequencing around the components and other sources of potential air leakage were used. This testing method is a major benefit to the design professional as issues such as air sealing and installation methods are dealt with by the manufacturer and proven in a controlled environment rather than the design professional using a trial and error method in the field.
The issue of installation is also dealt with in that the manufacturer must declare the level of skill required to assembly the various materials. When the assembly is put together for testing, the installers will have the skill level required and declared by the manufacturer. If there are no requirements – “anyone can do this”, then that is the type of person used to assemble the specimen for testing purposes. If the manufacturer sends his most qualified engineers to assemble the test specimen, then they are declaring that they must use people of this caliber to install their material in the field. Most manufacturers declare that their installers have to be trained in their installation instructions and prove that they have the knowledge to install the materials properly by being certified.
ABAA Evaluated Air Barrier Assemblies
| Self Adhered Sheets Materials | |||
|---|---|---|---|
| Manufacturer / Product | Air Leakage of Building Assembly (iaw ASTM E2357) | ||
| Grace Construction Products Perm-A-Barrier Wall Membrane |
< 0.004 L/(s • m2) @ 75 PA [< 0.0008 cfm /ft2 @ 1.57 psf] |
||
| Henry Company Blueskin® SA |
0.006 L/(s • m2) @ 75 PA [0.0012 cfm /ft2 @ 1.56 psf] |
||
| WR Meadows Air Shield |
0.0013 L/(s • m2) @ 75 PA [0.00026 cfm /ft2 @ 1.56 psf] |
||
| Fluid Applied Membranes | |||
|---|---|---|---|
| Manufacturer / Product | Air Leakage of Building Assembly (iaw ASTM E2357) | ||
| BASF Senershield-R, Finestop-RA, SonoWall FT-R, Acrostop-R and Enershield-HP |
0.0066 L/(s • m2) @ 75 PA [0.00132 cfm /ft2 @ 1.56 psf] @ 10 mils wet |
||
| DuPontTM Tyvek® Fluid Applied WB |
0.0036 L/(s • m2) @ 75 PA [0.0007 cfm /ft2 @ 1.56 psf] @ 25 mils wet |
||
| Grace Construction Products Perm-A-Barrier VP |
< 0.004 L/(s • m2) @ 75 PA [< 0.000787 cfm /ft2 @ 1.57 psf] @ 90 mils wet |
||
| Grace Construction Products Perm-A-Barrier Liquid |
< 0.004 L/(s • m2) @ 75 PA [< 0.000787 cfm /ft2 @ 1.57 psf] @ 40 mils wet |
||
| Henry Company Air Bloc 31 |
0.004 L/(s • m2) @ 75 PA [0.0008 cfm /ft2 @ 1.56 psf] @ 90 mils wet |
||
| Henry Company Air Bloc 32 |
0.0029 L/(s • m2) @ 75 PA [0.00058 cfm /ft2 @ 1.56 psf] @ 75 - 115 mils wet |
||
| Momentive Performance Materials SilShield AWB |
0.0064 L/(s • m2) @ 75 PA [0.0013 cfm /ft2 @ 1.56 psf] @ 18 mils wet [12 mils dry] |
||
| Parex USA Weatherseal |
0.0548 L/(s • m2) @ 75 PA [0.0108 cfm /ft2 @ 1.56 psf] @ 10 mils |
||
| Prosoco Inc. R-Guard Spray Wrap |
0.016 L/(s • m2) @ 75 PA [0.00311 cfm /ft2 @ 1.56 psf] |
||
| Prosoco Inc. R-Guard Fill |
0.012 L/(s • m2) @ 75 PA [0.00227 cfm /ft2 @ 1.56 psf] |
||
| Sto Corp. Gold Coat |
0.016 L/(s • m2) @ 75 PA [0.00311 cfm /ft2 @ 1.56 psf] |
||
| Sto Corp. Gold Fill |
0.012 L/(s • m2) @ 75 PA [0.00227 cfm /ft2 @ 1.56 psf] |
||
| STS Coatings Wall Guardian ® FW-100 Asphaltic-component |
< 0.0022 L/(s • m2) @ 75 PA [< 0.00043 cfm /ft2 @ 1.57 psf] @ 60 mils wet [35 mils dry] |
||
| STS Coatings FW-100-A Acrylic Based |
0.0006 L/(s • m2) @ 75 PA [0.00012 cfm /ft2 @ 1.57 psf] @ 20 mils dry |
||
| TK Products TK-AirMax 2102 NP (Non-Permeable), TK-AirMax 2102 OTC/LADCO |
0.005 L/(s • m2) @ 75 PA [0.0009 cfm /ft2 @ 1.56 psf] @ 32 mils wet |
||
| WR Meadows Air Shield LMP |
0.0026 L/(s • m2) @ 75 PA [0.00052 cfm /ft2 @ 1.56 psf] |
||
| WR Meadows Air Shield LM |
0.0035 L/(s • m2) @ 75 PA [0.0007 cfm /ft2 @ 1.56 psf] @ 60 mils wet |
||
| Sprayed Polyurethane Foam (Medium Density Closed Cell) | |||
|---|---|---|---|
| Manufacturer / Product | Air Leakage of Building Assembly (iaw ASTM E2357) | ||
| BASF Walltite |
0.0076 L/(s • m2) @ 75 PA [0.0015 cfm /ft2 @ 1.57 psf] @ 25mm [1.0"] |
||
| Bayer MaterialScience ECOBAY CC, ECOBAY CC POLAR |
0.0213 L/(s • m2) @ 75 PA [0.0043 cfm /ft2 @ 1.56 psf] @ 39mm [1.5"] |
||
| CertainTeed Insulation Group CertaSpray CC |
0.008 L/(s • m2) @ 75 PA [0.0016 cfm /ft2 @ 1.56 psf] @ 25mm [1.0"] |
||
| Henry Permax 2.0 |
< 0.0025 L/(s • m2) @ 75 PA [< 0.00049 cfm /ft2 @ 1.57 psf] @ 50mm [2.0"] |
||
| Icynene Inc. MD-C-200 |
0.0803 L/(s • m2) @ 75 PA [0.0161 cfm /ft2 @ 1.56 psf] @ 50mm [2.0"] |
||
| Johns Manville Corbond III |
0.0182 L/(s • m2) @ 75 PA [0.00364 cfm /ft2 @ 1.56 psf] @ 50mm [2.0"] |
||
| NCFI Polyurethanes InsulStar® and ThermalStop® |
0.0032 L/(s • m2) @ 75 PA [0.00064 cfm /ft2 @ 1.56 psf] @ 37mm [1.5"] |
||
| Mechanically Attached Flexible Sheet | |||
|---|---|---|---|
| Manufacturer / Product | Air Leakage of Building Assembly (iaw ASTM E2357) | ||
| DuPont Building Innovations Tyvek® CommercialWrap® |
0.05 L/(s • m2) @ 75 PA [0.01 cfm /ft2 @ 1.56 psf] |
||
| DuPont Building Innovations Tyvek® CommercialWrap® D |
0.0803 L/(s • m2) @ 75 PA [0. 0158 cfm /ft2 @ 1.56 psf] |
||
| Boardstock Air Barrier – Rigid Foam Core | |||
|---|---|---|---|
| Manufacturer / Product | Air Leakage of Building Assembly (iaw ASTM E2357) | ||
| Dow Chemical Company Thermax Wall System |
0.05 L/(s • m2) @ 75 PA [0.01 cfm /ft2 @ 1.56 psf] @ 5/8" [16mm] thick foam sheathing |
||
| Dow Chemical Company Ultra Wall Air Barrier System |
0.0803 L/(s • m2) @ 75 PA [0.01606 cfm /ft2 @ 1.56 psf] @ 1.5" [38mm] thick foam sheathing |
||