Evaluated Materials

AIR BARRIER MATERIALS WHICH HAVE COMPLETED THE ABAA EVALUATION PROCESS

ABAA Evaluated Air Barrier Materials

Self Adhered Sheet Materials Section 072761

Carlisle Coatings & Waterproofing www.carlisleccw.com

CCW-705
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.00 L/(s • m2) @ 75 Pa [0.000 cfm /ft2 @ 1.57 psf] 4.79 ng / Pa•s•m2 [0.083 US Perms] 5.47 ng / Pa•s•m2 [0.095 US Perms] 0.0222 L/(s • m2) @ 75 Pa
[0.0044 cfm /ft2 @ 1.57 psf]
Fire Resist 705 FR-A
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.00016 L/(s • m2) @ 75 Pa [0.000032 cfm /ft2 @ 1.57 psf] < 0.572 ng / Pa•s•m2 [[< 0.01 US Perms] < 0.572 ng / Pa•s•m2 [< 0.01 US Perms] 0.007 L/(s • m2) @ 75 Pa
[0.0014 cfm /ft2 @ 1.57 psf]

Cosella-Dörken Products Inc.www.cosella-dorken.com

DELTA-VENT SA
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.0015 L/(s • m2) @ 75 Pa [0.0003 cfm /ft2ÿ@ 1.57 psf] 1763 ng / Pa•s•m2[30.9 US Perms] 2830 ng / Pa•s•m2[49.5 US Perms] 0.039 L/(s • m2) @ 75 Pa
[0.0078 cfm /ft2@ 1.57 psf]

Grace Construction Productswww.na.graceconstruction.com

Perm-A-Barrier® Wall Membrane
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.001 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] 2.58 ng / Pa•s•m2 [0.05 US Perms] 3.06 ng / Pa•s•m2 [0.05 US Perms] < 0.004 L/(s • m2) @ 75 Pa [< 0.0008 cfm /ft2 @ 1.57 psf]

Henry Companywww.henry.com

Blueskin® SA
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.0002 L/(s • m2) @ 75 Pa [0.00004 cfm /ft2 @ 1.57 psf] 2.0 ng / Pa•s•m2 [0.03 US Perms] 49.0 ng / Pa•s•m2 [0.86 US Perms] 0.006 L/(s • m2) @ 75 Pa
[0.0012 cfm /ft2 @ 1.57 psf]

Soprema Inc.www.soprema.us

SopraSEAL Stick 1100T
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
< 0.0005 L/(s • m2) @ 75 Pa [0.0001 cfm /ft2 @ 1.57 psf] 0.89 ng / Pa•s•m2 [0.016 US Perms] 1.8 ng / Pa•s•m2 [0.031 US Perms] < 0.0022 L/(s • m2) @ 75 Pa [< 0.0004 cfm /ft2 @ 1.57 psf]
SopraSEAL STICK VP
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.0024 L/(s • m2) @ 75 Pa [0.00048 cfm /ft2 @ 1.57 psf] 614 ng / Pa•s•m2 [10.7 US Perms] 978 ng / Pa•s•m2 [17.1 US Perms] < 0.005 L/(s • m2) @ 75 Pa [< 0.001 cfm /ft2 @ 1.57 psf]

Tremcowww.tremcosealants.com

ExoAir 110
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.00005 L/(s • m2) @ 75 Pa [0.00001 cfm /ft2 @ 1.57 psf] 1.15 ng / Pa•s•m2 [0.02 US Perms] 1.26 ng / Pa•s•m2 [0.02 US Perms] 0.1147 L/(s • m2) @ 75 Pa
[0.02294 cfm /ft2 @ 1.57 psf]
ExoAir 111
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
< 0.0005 L/(s • m2) @ 75 Pa [[< 0.0001 cfm /ft2 @ 1.57 psf] 0.86 ng / Pa•s•m2 [0.01 US Perms] 2.28 ng / Pa•s•m2 [0.04 US Perms] 0.015 L/(s • m2) @ 75 Pa
[0.003 cfm /ft2 @ 1.57 psf]

W.R. Meadows, Inc.www.wrmeadows.com

Air Shield
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.0015 L/(s • m2) @ 75 Pa [0.0003 cfm /ft2 @ 1.57 psf] 1.01 ng / Pa•s•m2 [0.018 US Perms] 2.697 ng / Pa•s•m2 [0.047 US Perms] 0.0013 L/(s • m2) @ 75 Pa
[0.00026 cfm /ft2 @ 1.57 psf]

Fluid Applied Membranes Section 072726

BASF Corporation – Wall Systemswww.wallsystems.basf.com

Enershield-I, Senershield-VB, Finestop-VB
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0001 L/(s • m2) @ 75 Pa [0.0000 cfm /ft2 @ 1.57 psf] @ 26 mils (wet) 5.53 ng / Pa•s•m2 [0.097 US Perms] @ 20 mils (wet) 377 ng / Pa•s•m2 [6.58 US Perms] @ 20 mils (wet) 0.0055 L/(s • m2) @ 75 Pa
[0.0011 cfm /ft2 @ 1.57 psf] @ 10 mils wet
As required by manufacturer
Senershield® R, Acrostop R, Enershield™ HP, Finestop RA, SonoWall FT R
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0002 L/(s • m2) @ 75 Pa [0.0000 cfm /ft2 @ 1.57 psf] @ 10 mils (wet) 5.81 ng / Pa•s•m2 [0.10 US Perms] @ 10 mils (wet) 1004 ng / Pa•s•m2 [17.6 US Perms] @ 10 mils (wet) 0.0066 L/(s • m2) @ 75 Pa
[0.00132 cfm /ft2 @ 1.57 psf] @ 10 mils wet
As required by manufacturer

Carlisle Coatings & Waterproofingwww.carlisleccw.com

Barriseal-S/R
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0065 L/(s • m2) @ 75 Pa [0.0013 cfm /ft2 @ 1.57 psf] @ 46 mils (wet) 9.411 ng / Pa•s•m2 [0.1647 US Perms] @ 46 mils (dry) 48.745 ng / Pa•s•m2 [0.853 US Perms] @ 46 mils (dry) 0.012 L/(s • m2) @ 75 Pa
[0.00242 cfm /ft2 @ 1.57 psf] @ 65 mils (wet)
46 mils (wet)
Barritech VP/ Barritech VP LT
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.001 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] @ 65 mils (wet) 41.1 ng / Pa•s•m2 [0.719 US Perms] @ 60 mils (wet) [40 mils (dry)] 817 ng / Pa•s•m2 [14.295 US Perms] @ 60 mi ls (wet) [40 mils (dry)] 0.012 L/(s • m2) @ 75 Pa
[0.00242 cfm /ft2 @ 1.57 psf] @ 65 mils (wet)
65 mils (wet)
Fire-Resist Barritech NP
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.001 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] @ 80 mils (wet) [40 mils (dry)] 2.86 ng / Pa•s•m2 [0.05 US Perms] @ 35 mils (dry) 44 ng / Pa•s•m2 [0.77 US Perms] @ 35 mils (dry) 0.1167 L/(s • m2) @ 75 Pa
[0.0230 cfm /ft2 @ 1.57 psf] @ 80 mils (wet)
80 mils (wet)

Dow Corningwww.buildabetterbarrier.com

DefendAir 200
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0049 L/(s • m2) @ 75 Pa [0.00098 cfm /ft2 @ 1.57 psf] @ 15 mils (dry) 402.11 ng / Pa•s•m2 [7.03 US Perms] @ 15 mils (dry) 1387.7 ng / Pa•s•m2 [24.26 US Perms] @ 15 mils (dry) 0.00049 L/(s • m2) @ 75 Pa
[0.000098 cfm /ft2 @ 1.57 psf] @ 28 – 34 mils (dry)
15 mils (dry)

Dryvit Systems Inc.www.dryvit.com

Backstop NT
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0006 L/(s • m2) @ 75 Pa [0.000118 cfm /ft2 @ 1.57 psf] @ 12 mils (dry) 4.30 ng / Pa•s•m2 [0.075 US Perms] @ 20 mils (dry) 1810 ng / Pa•s•m2 [31.65 US Perms] @ 20 mils (dry) 12 mils (dry)

DuPont™www.fluidapplied.tyvek.com

Tyvek® Fluid Applied WB
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.001 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] @ 25 mils (dry) 656 ng / Pa•s•m2 [11.48 US Perms] @ 25 mils (dry) 1384 ng / Pa•s•m2 [24.23 US Perms] @ 25 mils (dry) 25 mils (wet)
25 mils (dry)

Grace Construction Productswww.na.graceconstruction.com

Perm-A-Barrier VP
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.002 L/(s • m2) @ 75 Pa [0.0004 cfm /ft2 @ 1.57 psf] @ 69 mils (wet) 34.39 ng / Pa•s•m2 [0.60 US Perms] @ 40 mils (dry) 741.6 ng / Pa•s•m2 [12.9 US Perms] @ 40 mils (dry) < 0.004 L/(s • m2) @ 75 Pa [< 0.000787 cfm /ft2 @ 1.57 psf] @ 90 mils wet 69 mils (wet)
Perm-A-Barrier Liquid
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
< 0.001 L/(s • m2) @ 75 Pa [< 0.0002 cfm /ft2 @ 1.57 psf] @ 51 mils (dry) 4.96 ng / Pa•s•m2 [0.09 US Perms] @ 60 mils (dry) 5.15 ng / Pa•s•m2 [0.09 US Perms] @ 60 mils (dry) < 0.004 L/(s • m2) @ 75 Pa [< 0.000787 cfm /ft2 @ 1.57 psf] @ 40 mils wet 51 mils (dry)

Henry Companywww.henry.com

Air Bloc 31MR
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0012 L/(s • m2) @ 75 Pa [0.00024 cfm /ft2 @ 1.57 psf] @ 87 mils (wet) 32.0 ng / Pa•s•m2 [0.57 US Perms] @ 44 mils (dry) 2066 ng / Pa•s•m2 [36.12 US Perms] @ 44 mils (dry) 0.004 L/(s • m2) @ 75 Pa
[0.0008 cfm /ft2 @ 1.57 psf] @ 90 mils wet
120 mils (wet)
Air Bloc 32MR
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0005 L/(s • m2) @ 75 Pa [0.0001 cfm /ft2 @ 1.57 psf] @ 118 mils (wet) 13.0 ng / Pa•s•m2 [0.23 US Perms] @ 118 mils (wet) 58 ng / Pa•s•m2 [1.02 US Perms] @ 118 mils (wet) 0.0029 L/(s • m2) @ 75 Pa
[0.00058 cfm /ft2 @ 1.57 psf] @ 75 – 115 mils wet
75-115 mils (wet)
Air Bloc 33MR
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0008 L/(s • m2) @ 75 Pa [0.0016 cfm /ft2 @ 1.57 psf] 19.0 ng / Pa•s•m2 [0.34 US Perms] @ 59 mils (dry) 652 ng / Pa•s•m2 [11.4 US Perms] @ 59 mils (dry) 0.0071 L/(s • m2) @ 75 Pa
[0.0014 cfm /ft2 @ 1.57 psf] @ 100 mils (wet) [58 mils (dry)]
100 mils (wet)
58 mils (dry)

Hohmann & Barnard, Incwww.h-b.com

Enviro-Barrier
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0004 L/(s • m2) @ 75 Pa [0.00008 cfm /ft2 @ 1.57 psf] @ 40 mils (dry) 3.40 ng / Pa•s•m2 [0.060 US Perms] @ 40 mils (dry) 39.6 ng / Pa•s•m2 [0.694 US Perms] @ 40 mils (dry) 0.0040 L/(s • m2) @ 75 Pa
[0.0008 cfm /ft2 @ 1.57 psf] @ 50 mils (wet)
40 mils (dry)

Laticretewww.laticrete.com

Air and Water Barrier
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.00052 L/(s • m2) @ 75 Pa [0.000104 cfm /ft2 @ 1.56 psf] @ 38 mils (wet) [25 mils (dry)] 4.92 ng / Pa•s•m2 [0.086 US Perms] @ 35 mils (wet) [25 mils (dry)] 57.3 ng / Pa•s•m2 [1.002 US Perms] @ 36 mils (wet) [26 mils (dry)] 0.0017 L/(s • m2) @ 75 Pa
[0.0003 cfm /ft2 @ 1.57 psf] @ 63 mils (dry)
20-30 mils (dry)

Masonry Foams and Coatingswww.masonryfoamsandcoatings.com

Air Smart VP
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0005 L/(s • m2) @ 75 Pa [0.0001 cfm /ft2 @ 1.57 psf] @ 32 mils (wet) 55.30 ng / Pa•s•m2 (0.96 US Perms) @ 22 mils (dry) 660.80 ng / Pa•s•m2 (11.5 US Perms) @ 22 mils (dry) 0.0022 L/(s • m2) @ 75 Pa
[0.00044 cfm /ft2 @ 1.57 psf] @ 20 mils (dry)
20 mils (dry)

Momentivewww.siliconeforbuilding.com/AWB

GE Elemax 2600
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.003 L/(s • m2) @ 75 Pa [0.0006 cfm /ft2 @ 1.57 psf] @ 17 mils (dry) 453.02 ng / Pa•s•m2 (7.92 US Perms) @ 17 mils (dry) 581.15 ng / Pa•s•m2 (10.16 US Perms) @ 17 mils (dry) 0.0009 L/(s • m2) @ 75 Pa
[0.0018 cfm /ft2 @ 1.57 psf] @ 19 mils (wet)
17 mils (dry)

Parex USAwww.parexusa.com

Weatherseal
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
< 0.00001 L/(s • m2) @ 75 Pa [0.000002 cfm /ft2 @ 1.57 psf] @ 12 mils (wet) 47.3 ng / Pa•s•m2 (0.828 US Perms) @ 30 mils (wet) 526 ng / Pa•s•m2 (9.2 US Perms) @ 18 mils (wet) 0.0548 L/(s • m2) @ 75 Pa
[0.0108 cfm /ft2 @ 1.57 psf] @ 10 mils
“12 mils (wet)
2 x 10 mils rolled, spray and trowel”
6 mils (dry)

Pecora Corpationwww.pecora.com

XL-Perm ultra VP
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0012 L/(s • m2) @ 75 Pa [0.00024 cfm /ft2 @ 1.57 psf] @ 12 mils (dry) 653.22 ng / Pa•s•m2 (11.42 US Perms) @ 9 mils (dry) 727.01 ng / Pa•s•m2 (12.71 US Perms) @ 9 mils (dry) 0.0040 L/(s • m2) @ 75 Pa
[0.0008 cfm /ft2 @ 1.57 psf] @ 14 mils (wet)
9-12 mils (dry)

Polyguard Products Inc.www.poly-wall.com

Poly Wall AirLok Flex
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.00195 L/(s • m2) @ 75 Pa [0.0039 cfm /ft2 @ 1.57 psf] @ 1gal/70ft2 3.32 ng / Pa•s•m2 (0.058 US Perms) @ 40 mils (wet), 20 mils (dry) 12.5 ng / Pa•s•m2 (0.219 US Perms) @ 40 mils (wet), 20 mils (dry) 0.004 L/(s • m2) @ 75 Pa
[0.0008 cfm /ft2 @ 1.57 psf] @ 16 mils (dry)
12 mils (dry)
Airlok Flex WG
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.000024 L/(s • m2) @ 75 Pa [0.0000048 cfm /ft2 @ 1.57 psf] @ 33 mils (wet) 199.19 ng / Pa•s•m2 (3.49 US Perms) @ 10 mils (dry) 1186.88 ng / Pa•s•m2 (20.77 US Perms) @ 10 mils (dry) 0.011 L/(s • m2) @ 75 Pa
[0.0022 cfm /ft2 @ 1.57 psf] @ 20 mils (wet)
33 mils (wet)

Prosoco Inc.www.prosoco.com

R-Guard™ Cat 5
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0009 L/(s • m2) @ 75 Pa [0.00018 cfm /ft2 @ 1.56 psf] @ 12 mils (dry) 859 ng / Pa•s•m2 (15.03 US Perms) @ 12-15 mils (wet) 1015 ng / Pa•s•m2 (17.71 US Perms) @ 12-15 mils (wet) 0.0107 L/(s • m2) @ 75 Pa
[< 0.0021 cfm /ft2 @ 1.57 psf] @ 12 - 16 mils (wet)
12-15 mils (wet)
R-Guard™ Fill
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0014 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] 107 ng / Pa•s•m2 (1.87 US Perms) @ 27 mils (wet) 480 ng / Pa•s•m2 (8.40 US Perms) @ 30 mils (wet) 0.012 L/(s • m2) @ 75 Pa
[0.00227 cfm /ft2 @ 1.57 psf] @ 32 – 63 mils
10 mils (wet)
R-Guard™ Spray Wrap
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.000 L/(s • m2) @ 75 Pa [0.0000 cfm /ft2 @ 1.57 psf] @ 10-12 mils (wet) 6.86 ng / Pa•s•m2 (0.12 US Perms) @ 12 mils (wet) 202 ng / Pa•s•m2 (3.54 US Perms) @ 12 mils (wet) 0.016 L/(s • m2) @ 75 Pa
[0.00311 cfm /ft2 @ 1.57 psf] @ 10 – 20 mils (wet)
10-12 mils (wet)
R-Guard™ Spray Wrap MVP
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.001 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] @ 26 mils (dry) 311.74 ng / Pa•s•m2 (5.45 US Perms) @ 5 mils (dry) 1944 ng / Pa•s•m2 (34.43 US Perms) @ 5 mils (dry) 0.003 L/(s • m2) @ 75 Pa
[0.0006 cfm /ft2 @ 1.57 psf] @ 10 mils (dry)
26 mils (dry)

Protecto Wrapwww.protectowrap.com

Protecto Wall Liquid Air Barrier VP
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0043 L/(s • m2) @ 75 Pa [0.00086 cfm /ft2 @ 1.57 psf] @ 10 mils (dry) 55.3 ng / Pa•s•m2 (0.96 US Perms) @ 22 mils (dry) 660.8 ng / Pa•s•m2 (11.5 US Perms) @ 22 mils (dry) 0.0022 L/(s • m2) @ 75 Pa
[0.00044 cfm /ft2 @ 1.57 psf] @ 20 mils (dry)
10 mils (dry)

Sika Corp.usa.sika.com

Sikagard 530 Liquid Applied Vapor Permeable Air Barrier
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0005 L/(s • m2) @ 75 Pa [< 0.0001 cfm /ft2 @ 1.57 psf] @ 20 mils (dry) 55.3 ng / Pa•s•m2 (0.96 US Perms) @ 22 mils (dry) 661 ng / Pa•s•m2 (11.5 US Perms) @ 22 mils (dry) < 0.0022 L/(s • m2) @ 75 Pa [< 0.00043 cfm /ft2 @ 1.57 psf] @ 20 mils (dry) 30 mils (dry)
Sikagard 520 Liquid Applied Vapor Permeable Air Barrier
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0069 L/(s • m2) @ 75 Pa [0.0014 cfm /ft2 @ 1.57 psf] @ 30 mils (dry) < 5.7 ng / Pa•s•m2 (< 0.1 US Perms) @ 30 mils (dry) 720 ng / Pa•s•m2 (12.6 US Perms) @ 30 mils (dry) < 0.0022 L/(s • m2) @ 75 Pa [< 0.00043 cfm /ft2 @ 1.57 psf] @ 60 mils (wet) [35 mils (dry)] 30 mils (dry)

Sopremawww.soprema.us

Sopraseal LM 202 VP
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0002 L/(s • m2) @ 75 Pa [0.0000 cfm /ft2 @ 1.57 psf] @ 10 mils (wet) 5.81 ng / Pa•s•m2 (0.10 US Perms) @ 10 mils (wet) 1004 ng / Pa•s•m2 (17.6 US Perms) @ 10 mils (wet) 0.0066 L/(s • m2) @ 75 Pa
[0.00132 cfm /ft2 @ 1.57 psf] @ 10 mils (wet)
10 mils (wet)
Sopraseal LM 203
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0001 L/(s • m2) @ 75 Pa [0.00002 cfm /ft2 @ 1.57 psf] @ 26 mils (wet) 5.53 ng / Pa•s•m2 (0.097 US Perms) @ 20 mils (wet) 377 ng / Pa•s•m2 (6.58 US Perms) @ 20 mils (wet) 0.0066 L/(s • m2) @ 75 Pa
[0.00132 cfm /ft2 @ 1.57 psf] @ 10 mils (wet)
26 mils (wet)

Sto Corp.www.stocorp.com

EmeraldCoat
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.00020 L/(s • m2) @ 75 Pa [0.00024 cfm /ft2 @ 1.57 psf] @ 20 mils (dry) 121.26 ng / Pa•s•m2 (2.12 US Perms) @ 12 mils (dry) 797.94 ng / Pa•s•m2 (13.95 US Perms) @ 12 mils (wet) 0.0008 L/(s • m2) @ 75 Pa
[0.00016 cfm /ft2 @ 1.57 psf] @ 10 mils (wet)
20 mils (dry)
Gold Coat
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.000 L/(s • m2) @ 75 Pa [0.0000 cfm /ft2 @ 1.57 psf] @ 10-12 mils (wet) 6.86 ng / Pa•s•m2 (0.12 US Perms) @ 12 mils (wet) 202 ng / Pa•s•m2 (3.54 US Perms) @ 12 mils (wet) 0.016 L/(s • m2) @ 75 Pa
[0.00311 cfm /ft2 @ 1.57 psf] @ 10 – 20 mils (wet)
10-12 mils (wet)
Gold Fill
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0014 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] 107 ng / Pa•s•m2 (1.87 US Perms) @ 27 mils (wet) 480 ng / Pa•s•m2 (8.40 US Perms) @ 30 mils (wet) 0.012 L/(s • m2) @ 75 Pa
[0.00227 cfm /ft2 @ 1.57 psf] @ 32 – 63 mils
10 mils (wet)
VaporSeal
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.01623 L/(s • m2) @ 75 Pa [0.004 cfm /ft2 @ 1.56 psf] @ 32 – 48 mils (wet) 2.52 ng / Pa•s•m2 (0.044 US Perms) @ 30 mils (dry) 32.6 ng / Pa•s•m2 (0.57 US Perms) @ 26 mils (dry) 0.011 L/(s • m2) @ 75 Pa
[0.00215 cfm /ft2 @ 1.57 psf] @ 32 – 48 mils (wet)
46-74 mils (wet)

Kemper Systems America Inc.www.kemper-system.com

Wall Guardian® FW-100 Asphaltic-component
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0069 L/(s • m2) @ 75 Pa [0.001358 cfm /ft2 @ 1.57 psf] at 30 mils (dry) [60 mils (wet)] < 5.72 ng / Pa•s•m2 [< 0.10 US Perms] @ 30 mils (dry) 720 ng / Pa•s•m2 [12.6 US Perms] @ 30 mils (dry) < 0.0022 L/(s • m2) @ 75 Pa [< 0.00043 cfm /ft2 @ 1.57 psf] @ 60 mils wet [35 mils dry] 60 mils (wet)
30 mils (dry)
Wall Guardian® FW-100-A Acrylic Based
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0005 L/(s • m2) @ 75 Pa [0.0001 cfm /ft2 @ 1.57 psf] at 20 mils (dry) 55.3 ng / Pa•s•m2 [0.96 US Perms] @ 22 mils (dry) 661 ng / Pa•s•m2 [11.5 US Perms] @ 22 mils (dry) < 0.0022 L/(s • m2) @ 75 Pa [0.0004 cfm /ft2 @ 1.57 psf] @ 20 mils dry 40 mils (wet)
20 mils (dry)

TK Productswww.tkproducts.com

TK-AirMax 2102 (Non-Permeable), TK-AirMax 2102 (Non-Permeable VOC)
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.002 L/(s • m2) @ 75 Pa [0.0004 cfm /ft2 @ 1.57 psf] @ 40+ mils (wet) 0.751 ng / Pa•s•m2 [0.013 US Perms] @ 20 mils (dry) 6.29 ng / Pa•s•m2 [0.11 US Perms] @ 12 mils (dry) 0.005 L/(s • m2) @ 75 Pa
[0.0009 cfm /ft2 @ 1.57 psf] @ 32 mils wet
40-45+ mils (wet)
TK-AirMax 2103 (Water-Based)
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.00492 L/(s • m2) @ 75 Pa [0.00097 cfm /ft2 @ 1.57 psf] @ 40 mils (wet) 6.699 ng / Pa•s•m2 [0.117 US Perms] @ 19.3 mils (dry) 857 ng / Pa•s•m2 [15.0 US Perms] @ 19.7 mils (dry) 0.006 L/(s • m2) @ 75 Pa
[0.0013 cfm /ft2 @ 1.57 psf] @ 32 mils wet
40 mils (wet)
TK-AirMax 2104 (Water Base)
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.004 L/(s • m2) @ 75 Pa [0.0008 cfm /ft2 @ 1.57 psf] @ 40+ mils (wet) 17.1 ng / Pa•s•m2 [0.3 US Perms] @ 12.1 mils (dry) 1007 ng / Pa•s•m2 [17.6 US Perms] @ 14 mils (dry) 0.024 L/(s • m2) @ 75 Pa
[0.0047 cfm /ft2 @ 1.57 psf] @ 32 mils wet [22 mils dry]
40+ mils (wet)

Tremcowww.tremcosealants.com

ExoAir 230
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.00011 L/(s • m2) @ 75 Pa [0.00030 cfm /ft2 @ 1.57 psf] @ 40 mils (wet) 103.72 ng / Pa•s•m2 [1.81 US Perms] @ 29 mils (dry) 1677 ng / Pa•s•m2 [29.31 US Perms] @ 29 mils (dry) <0.05 L/(s • m2) @ 75 Pa [0.01 cfm /ft2 @ 1.57 psf] @ 35 mils dry 40 mils (wet)

W.R. Meadows, Inc.www.wrmeadows.com

Air Shield LMP
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0011 L/(s • m2) @ 75 Pa [0.00022 cfm /ft2 @ 1.57 psf] @ 20 mils (dry) 9.62 ng / Pa•s•m2 [0.168 US Perms] @ 47.6 mils (dry) 598 ng / Pa•s•m2 [10.47 US Perms] @ 47.6 mils (dry) 0.0026 L/(s • m2) @ 75 Pa
[0.00052 cfm /ft2 @ 1.57 psf] @ 90 mils (wet) [45 mils dry]
20 mils (dry)

Sprayed Polyurethane Foam (Medium Density Closed Cell) Section 072703

BASF – The Chemical Groupwww.walltite.com

Walltite
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.00032 L/(s • m2) @ 75 Pa [0.000064 cfm /ft2 @ 1.57 psf] @ 32mm [1.3″] 79.6 ng / Pa•s•m2 [1.39 US Perms] @ 25mm [1.0″] 241 ng / Pa•s•m2 [4.22 US Perms] @ 25mm [1.0″] 0.0076 L/(s • m2) @ 75 Pa
[0.0015 cfm /ft2 @ 1.57 psf] @ 25mm [1.0″]
Minimum 25mm

Bayer MaterialSciencewww.spf.bayermaterialscience.com

ECOBAY CC, ECOBAY CC POLAR
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.00011 L/(s • m2) @ 75 Pa [0.000023 cfm /ft2 @ 1.57 psf] 34.5 ng / Pa•s•m2 [0.603 US Perms] @ 33mm [1.3″] 56 ng / Pa•s•m2 [0.979 US Perms] @ 50mm [2.0″] 0.0213 L/(s • m2) @ 75 Pa
[0.0043 cfm /ft2 @ 1.57 psf] @ 39mm [1.5″]
Minimum 25mm

CertainTeed Corporationwww.certainteed.com

CertaSpray CC
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.00076 L/(s • m2) @ 75 Pa [0.000152 cfm /ft2 @ 1.57 psf] @ 27mm [1.06″] 56 ng / Pa•s•m2 [0.98 US Perms] @ 36mm [1.42″] 102 ng / Pa•s•m2 [1.79 US Perms] @ 47mm [1.85″] 0.008 L/(s • m2) @ 75 Pa
[0.0016 cfm /ft2 @ 1.57 psf] @ 25mm [1.0″]
Minimum 25mm

Demilecwww.demilec.com

Heatlok Soy 200 Plus
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.004 L/(s • m2) @ 75 Pa [0.0008 cfm /ft2 @ 1.57 psf] @ 25mm [1.0″] 1.131 US Perms @ 25mm [1.0″] 0.0022 L/(s • m2) @ 75 Pa
[0.00044 cfm /ft2 @ 1.57 psf] @ 100mm [4.0″]
Minimum 25mm
Heatlok XT
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.020 L/(s • m2) @ 75 Pa [0.004 cfm /ft2 @ 1.57 psf] @ 25mm 70.5 ng / Pa•s•m2 [1.23 US Perms] @ 25mm 119 ng / Pa•s•m2 [2.08 US Perms] @ 25mm 0.0383 L/(s • m2) @ 75 Pa
[0.0076 cfm /ft2 @ 1.57 psf] @ 50mm [2.0″]
Minimum 25mm

Gaco Westernwww.gaco.com

Gaco WallFoam 183M
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0013 L/(s • m2) @ 75 Pa [0.0003 cfm /ft2 @ 1.57 psf] @ 36mm [1.42″] 35.9 ng / Pa•s•m2 [0.628 US Perms] @ 50mm [2.0″] 63 ng / Pa•s•m2 [1.1 US Perms] @ 50mm [2.0″] 0.00273 L/(s • m2) @ 75 Pa
[0.000546 cfm /ft2 @ 1.57 psf] @ 25mm [1.0″]
Minimum 25mm

Henry Companywww.henry.com

Permax 2.0
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0005 L/(s • m2) @ 75 Pa [0.000098 cfm /ft2 @ 1.57 psf] 27 ng / Pa•s•m2 [0.472 US Perms] @ 52.8mm [2.078″] 84 ng / Pa•s•m2 [1.46 US Perms] @ 63.5mm [2.5″] < 0.0025 L/(s • m2) @ 75 Pa [< 0.00049 cfm /ft2 @ 1.57 psf] @ 50mm [2.0"] Minimum 25mm

Icynene Inc.www.icynene.com

MD-C-200
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0008 L/(s • m2) @ 75 Pa [0.00016 cfm /ft2 @ 1.57 psf] @ 52mm [2.05″] 50.6 ng / Pa•s•m2 [0.884 US Perms] @ 37mm [1.5″] 2748 ng / Pa•s•m2 [48.09 US Perms] @ 50mm [2.0″] 0.0803 L/(s • m2) @ 75 Pa
[0.0161 cfm /ft2 @ 1.57 psf] @ 50mm [2.0″]
Minimum 25mm
ProSeal (MD-C-200-v3)
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.00150 L/(s • m2) @ 75 Pa [0.00030 cfm /ft2 @ 1.57 psf] @ 32 mm [1.29″] 68.9 ng / Pa•s•m2 [1.205 US Perms] @ 25mm [1.0″] 74 ng / Pa•s•m2 [1.3 US Perms] @ 50mm [1.0″] 0.0106 L/(s • m2) @ 75 Pa
[0.00212 cfm /ft2 @ 1.57 psf] @ 25mm [1.0″]
Minimum 25mm

Johns Manvillewww.specjm.com

Corbond III
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.000244 L/(s • m2) @ 75 Pa [0.000049 cfm /ft2 @ 1.57 psf] @ 50mm [2.0″] 53 ng / Pa•s•m2 [0.927 US Perms] @ 50mm [2.0″] 120 ng / Pa•s•m2 [2.0 US Perms] @ 25mm [1.0″] 0.0915 L/(s • m2) @ 75 Pa
[0.0183 cfm /ft2 @ 1.57 psf] @ 37mm [1.5″]
Minimum 25mm

NCFI Polyurethaneswww.ncfi.com

InsulStar®, InsulBloc®
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0003 L/(s • m2) @ 75 Pa [0.00005 cfm /ft2 @ 1.57 psf] @ 25mm [1″] 56 ng / Pa•s•m2 [0.97 US Perms] @ 20mm [0.80″] 134 ng / Pa•s•m2 [2.35 US Perms] @ 20mm [0.80″] 0.0032 L/(s • m2) @ 75 Pa
[0.00064 cfm /ft2 @ 1.57 psf] @ 37mm [1.5″]
Minimum 25mm

Lapolla Industries Inc.www.lapolla.com

Foam-Lok AB2000
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.000244 L/(s • m2) @ 75 Pa [0.000049 cfm /ft2 @ 1.57 psf] @ 50mm [2.0″] 49 ng / Pa•s•m2 [0.8 US Perms] @ 50mm [1.97″] 90 ng / Pa•s•m2) [1.58 US Perms) @ 50mm [2.0″] 0.0915 L/(s • m2) @ 75 Pa
[0.0183 cfm /ft2 @ 1.57 psf] @ 37mm [1.5″]
Minimum 25mm

Mechanically Fastened Commercial Building Wrap Section 072708

DuPont Building Innovationswww.weatherization.tyvek.com

Tyvek® CommercialWrap®
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.0023 L/(s • m2) @ 75 Pa [0.00046 cfm /ft2 @ 1.57 psf] 1446 ng / Pa•s•m2 [25.31 US Perms] 1867 ng / Pa•s•m2 [32.68 US Perms] 0.05 L/(s • m2) @ 75 Pa
[0.01 cfm /ft2 @ 1.57 psf]
Tyvek® CommercialWrap® D
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.00225 L/(s • m2) @ 75 Pa [0.00045 cfm /ft2 @ 1.57 psf] 2437 ng / Pa•s•m2 [42.65 US Perms] 2427 ng / Pa•s•m2 [42.48 US Perms] 0.0803 L/(s • m2) @ 75 Pa
[0.0158 cfm /ft2 @ 1.57 psf]

Kingspan Insulation LLCwww.kingspaninsulation.com

GreenGuard® Max Building Wrap
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Air Leakage of Building Assembly (ASTM E2357)
< 0.001 L/(s • m2) @ 75 Pa [< 0.0002 cfm /ft2 @ 1.57 psf] 773 ng / Pa•s•m2 [13.52 US Perms] < 0.05 L/(s • m2) @ 75 Pa [< 0.01 cfm /ft2 @ 1.57 psf]
GreenGuard® RainDrop Building Wrap
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Air Leakage of Building Assembly (ASTM E2357)
< 0.001 L/(s • m2) @ 75 Pa [< 0.0002 cfm /ft2 @ 1.57 psf] 705 ng / Pa•s•m2 [12.33 US Perms] < 0.05 L/(s • m2) @ 75 Pa [< 0.01 cfm /ft2 @ 1.57 psf]
GreenGuard® C2000
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Air Leakage of Building Assembly (ASTM E2357)
< 0.003 L/(s • m2) @ 75 Pa [< 0.0006 cfm /ft2 @ 1.56 psf] 5377 ng / Pa•s•m2 [94 US Perms] < 0.05 L/(s • m2) @ 75 Pa [< 0.01 cfm /ft2 @ 1.57 psf]

Boardstock – Rigid Cellular Thermal Insulation Board Section 072723

Dow Chemical Companywww.dow.com

Styrofoam Ultra SL
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0012 L/(s • m2) @ 75 Pa [0.00023 cfm /ft2 @ 1.57 psf] @ 1.0″ [25mm] thick foam sheathing <62.9 ng / Pa•s•m2 [<1.1 US Perms] @ 1.0" [25mm] thick foam sheathing 0.02072 L/(s • m2) @ 75 Pa
[0.004144 cfm /ft2 @ 1.57 psf] @ 1.75″ [44mm] thick foam sheathing
Minimum 25mm
Thermax Wall System
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.001 L/(s • m2) @ 75 Pa [0.0002 cfm /ft2 @ 1.57 psf] @ 1/2″ [13mm] thick foam sheathing 2.29 ng / Pa•s•m2 [0.04 US Perms] @ 1.0″ [25mm] thick foam sheathing 333333333333333 0.05 L/(s • m2) @ 75 Pa
[0.01 cfm /ft2 @ 1.57 psf] @ 5/8″ [16mm] thick foam sheathing
Minimum 13mm
Ultra Wall Air Barrier System
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0012 L/(s • m2) @ 75 Pa [0.00023 cfm /ft2 @ 1.57 psf] @ 1.0″ [25mm] thick foam sheathing <62.9 ng / Pa•s•m2 [<1.1 US Perms] @ 1.0" [25mm] thick foam sheathing 0.0803 L/(s • m2) @ 75 Pa
[0.01606 cfm /ft2 @ 1.57 psf] @ 1.5″ [38mm] thick foam sheathing
Minimum 25mm

Johns Manvillewww.specjm.com

AP Foil-Faced
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357) Thickness
0.0007 L/(s • m2) @ 75 Pa [0.00013 cfm /ft2 @ 1.57 psf] @ 1.0″ [25mm] thick foam sheathing 3 ng / Pa•s•m2 [0.06 US Perms] @ 1.0″ [25mm] thick foam sheathing 0.0064 L/(s • m2) @ 75 Pa
[0.00128 cfm /ft2 @ 1.57 psf] @ 1.0″ [25mm] thick foam sheathing
Minimum 25mm

Factory-Bonded Membranes to Sheathing ABAA Model Spec currently in development

Sopremawww.soprema.ca

Sopraseal Xpress G
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.00834 L/(s • m2) @ 75 Pa [0.001668 cfm /ft2 @ 1.57 psf] 1.22 ng / Pa•s•m2 [0.0214 US Perms] 1.10 ng / Pa•s•m2 [0.0193 US Perms] 0.038 L/(s • m2) @ 75 Pa
[0.0076 cfm /ft2 @ 1.57 psf]

Georgia-Pacificwww.buildgp.com

Dens Element Barrier System
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.00510 L/(s • m2) @ 75 Pa [0.00086 cfm /ft2 @ 1.57 psf] – 5/8th board 55.30 ng / Pa•s•m2 [22.9 US Perms] – 5/8th board 660.80 ng / Pa•s•m2 [22.42 US Perms] – 5/8th board 0.0802 L/(s • m2) @ 75 Pa
[0.01604 cfm /ft2 @ 1.57 psf]

USG / Tremcowww.securockexoair.com

Securock ExoAir 430 System
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.0001 L/(s • m2) @ 75 Pa [< 0.00002 cfm /ft2 @ 1.57 psf] 105.24 ng / Pa•s•m2 [1.84 US Perms] 279.70 ng / Pa•s•m2 [4.89 US Perms] < 0.02 L/(s • m2) @ 75 Pa [< 0.004 cfm /ft2 @ 1.57 psf]

Adhesive Backed Commercial Building Wrap ABAA Model Spec currently in development

Cosella-Dörken Products Inc.www.cosella-dorken.com

DELTA-VENT SA
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.0015 L/(s • m2) @ 75 Pa [0.0003 cfm /ft2 @ 1.57 psf] 1763 ng / Pa•s•m2 [30.9 US Perms] 2830 ng / Pa•s•m2 [49.5 US Perms] 0.039 L/(s • m2) @ 75 Pa
[0.0078 cfm /ft2 @ 1.57 psf]

Soprema Inc.www.soprema.us

SopraSEAL STICK VP
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.0024 L/(s • m2) @ 75 Pa [0.00048 cfm /ft2 @ 1.57 psf] 614 ng / Pa•s•m2 [10.7 US Perms] 978 ng / Pa•s•m2 [17.1 US Perms] < 0.005 L/(s • m2) @ 75 Pa [< 0.001 cfm /ft2 @ 1.57 psf]

Vaproshieldwww.vaproshield.com

REVEALSHIELD SA
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.0001 L/(s • m2) @ 75 Pa [0.00002 cfm /ft2 @ 1.57 psf] 1600 ng / Pa•s•m2 [28.07 US Perms] 3630 ng / Pa•s•m2 [63.48 US Perms] <0.01 L/(s • m2) @ 75 Pa [<0.01 cfm /ft2 @ 1.57 psf]
WRAPSHIELD SA
Test Results

Air Permeance (ASTM E2178)

Water Vapor Permeance (ASTM E96 – desiccant method) Water Vapor Permeance (ASTM E96 – water method) Air Leakage of Building Assembly (ASTM E2357)
0.0001 L/(s • m2) @ 75 Pa [0.00002 cfm /ft2 @ 1.57 psf] 1630 ng / Pa•s•m2 [28.46 US Perms] 2510 ng / Pa•s•m2 [43.85 US Perms] <0.01 L/(s • m2) @ 75 Pa [<0.01 cfm /ft2 @ 1.57 psf]

If you have any questions please contact the ABAA office by email at abaa@airbarrier.org or by phone at 866-956-5888.